← All terms

Glossary · Energy industry & energy transition

IEC 62351

IEC 62351 is an international series of standards from the International Electrotechnical Commission (IEC) with the overall title "Power systems management and associated information exchange – Data and communications security". It is developed in Technical Committee TC 57, which is also responsible for the functional communication standards of the energy supply sector. The series describes how protocols, data models and access can be secured in control and automation technology, grid automation and substation communication. This includes authentication, integrity protection, encryption, role-based access control, key and certificate management, and the detection and reporting of security events.

IEC 62351 is neither a product nor a complete security programme of a grid operator. The series supplements functional communication standards with security mechanisms. According to the introductory part, it is aimed primarily at the TC 57 protocol series IEC 60870-5 (telecontrol protocols such as IEC 60870-5-101 and -104), IEC 60870-6 (ICCP/TASE.2 for data exchange between control centres), IEC 61850 (communication in substations and plants), and IEC 61970 and IEC 61968, on which the Common Information Model (CIM) is based. These functional standards define how protection devices, bays, control centres and grid control systems exchange data. IEC 62351 adds how this exchange can be protected against eavesdropping, manipulation, replay attacks and forged identities.

The need for this series stems from the history of the protocols. Many control technology protocols were created for environments that were protected mainly by physical separation, private networks and organisational trust. A command was considered authorised because it came from the expected network segment. A measured value was processed because it arrived in the right format. This model fits today's operating environments poorly: substations are more strongly networked, remote maintenance is widespread, digital protection and automation systems communicate over IP networks, and the number of interfaces between grid operation, plant operators and service providers is growing.

IEC 62351 therefore starts with the communication itself. A channel should not be regarded as secure merely because it lies within an isolated network. The remote end must identify itself, messages must arrive unaltered, access must match a role, and keys must be managed over their entire lifecycle. This is familiar from office IT, but operational technology in power supply is subject to different constraints: assets run for decades, availability requirements are high, switching responsibilities are clearly regulated, and some messages must arrive within a few milliseconds.

Structure of the series

The series consists of many parts with different status: International Standards (IS), Technical Specifications (TS) and Technical Reports (TR). The following overview lists the most important parts. Before any procurement, the edition currently in force should always be checked in the IEC catalogue, because several parts have been fundamentally revised in recent years.

  • Parts 1 and 2: introduction to the security issues of power system control technology and a glossary of terms.

  • Part 3 (Edition 2.0, June 2023): TLS profile for TCP/IP-based protocols, including SCADA and telecontrol protocols. Unlike earlier editions, Part 3 specifies all TLS parameters itself. These include mandatory cipher suites for TLS 1.2, a profile for TLS 1.3, requirements for session resumption and renegotiation, checking for revoked certificates via CRL and OCSP, and security events. Upstream external security devices ("bump-in-the-wire") are outside the scope.

  • Part 4: security for protocols based on MMS (Manufacturing Message Specification). This affects ICCP/TASE.2 and client-server communication under IEC 61850. In addition to transport protection, authentication at the application level is also provided for.

  • Part 5 (2023 edition): security at the application level for IEC 60870-5 and protocols derived from it. Because of this lineage, the part is also mentioned in connection with DNP3. The 2023 edition is a technical revision: protection is now provided per association between controlling and controlled station, the earlier challenge-reply procedure was removed, and authenticated encryption of application data was added.

  • Part 6 (2020 edition): security for IEC 61850 profiles. It covers the MMS mapping under IEC 61850-8-1, XMPP under IEC 61850-8-2, Sampled Values under IEC 61850-9-2 and the configuration language SCL. For the time-critical GOOSE and Sampled Value messages on layer 2, it contains, among other things, protection against replay attacks.

  • Part 7: data objects for network and system management (NSM), which can be used to monitor the state, performance and possible attacks on devices and communication links.

  • Part 8: role-based access control (RBAC). Part 9: management of keys and certificates. Part 10: technical report with guidelines on security architecture. Part 11: security for XML files. There are further parts, such as recommendations for systems with distributed generation and for the logging of security events.

Important in practice: the mechanisms only take effect when the specifications of the functional protocols adopt them and refer to them. For IEC 60870-5-101 and IEC 60870-5-104, this is done by the Technical Specification IEC TS 60870-5-7:2025. It describes the message formats and adaptations by which IEC 62351-5:2023 is implemented in these protocols. IEC 60870-5-104 uses it together with the TLS profile from IEC 62351-3:2023. For IEC 60870-5-103, this specification provides no separate protection. Those who need security there are referred to IEC 61850 with the mechanisms from IEC 62351.

Delimitation from neighbouring standards

IEC 62351 is often confused with general standards on cybersecurity. ISO/IEC 27001 describes an information security management system, that is, processes, responsibilities, risk treatment, audits and continual improvement. IEC 62443 addresses industrial automation systems as a whole, including zones, communication channels (conduits), requirements for components and security levels. IEC 62351 is narrower in scope. It describes how specific protocols and data models of energy technology can be operated more securely.

IEC 62351 is also not the same as IEC 61850. IEC 61850 models functions and communication services in substations and defines how a protection device, a measured value or a control command is structured and transmitted. IEC 62351 supplements this communication with security mechanisms. Using IEC 61850 therefore does not mean that IEC 62351 has automatically been implemented.

The term OT security is broader still. It covers network segmentation, hardening, patch management, monitoring, emergency and restart processes, and supplier management. IEC 62351 provides important building blocks for this at the level of protocols and data models, but does not replace a security architecture for control centres, substations and communication networks.

Which protection goals the mechanisms address

Authentication means that communication partners prove their identity, usually via X.509 certificates or shared keys. A control system should be able to tell whether it is really talking to a particular substation or gateway. Integrity protection means that a message cannot be altered unnoticed. Encryption protects the confidentiality of measurement, operational or configuration data. Role-based access control assigns actions to specific permissions, because reading, switching, parameterising and administering are not equivalent in grid operation.

Substation communication shows how strongly the solutions depend on the constraints. GOOSE messages and Sampled Values are distributed as multicast on layer 2, without a connection in the TCP sense. TLS is therefore not applicable here. In addition, transmission times of a few milliseconds apply to protection applications. The first version of Part 6 from 2007 relied on digital signatures, which the technical literature regarded as too computationally demanding for these timing requirements. The 2020 edition provides for these messages check values (message authentication codes) with group keys and protection against replay attacks. Encryption is only optional there. It follows that integrity and proof of origin take priority for protection signals, not confidentiality.

The protection goals do not replace one another. An encrypted channel does not prevent an unauthorised switching command if the remote end is technically connected but not authorised in functional terms. A role model is of little use if certificates are not maintained or private keys are stored insecurely. Integrity protection only helps if systems handle invalid, expired or revoked credentials in a controlled way. Part 3 does define security events for this purpose, but expressly leaves the response to them to the security policy of the respective organisation.

Significance for grid operation and security of supply

In the power system, false information and unauthorised commands can have physical consequences. Manipulated measured values can mislead grid control. Forged status messages can create a false picture of switching states. Unauthorised control commands can stress equipment, disrupt protection or complicate grid restoration. IEC 62351 is therefore less a matter of data protection than a matter of reliable operational management and thus of security of supply.

This becomes particularly important at interfaces where previously separate domains are growing together. Distributed generation plants, battery storage systems, controllable loads and virtual power plants create far more communication relationships than a system with a few large power stations. As the number of handover points between plant operators, direct marketers, distribution and transmission system operators, service providers and manufacturers grows, so does the attack surface. A security model that protects only the outer perimeter of the network is then no longer sufficient.

For grid operators, IEC 62351 also plays a role in procurement and integration. Requirements must be stated concretely in tenders, acceptance tests and migration plans, that is, with part and edition, for example IEC 62351-3:2023 with the TLS 1.3 profile. A device that supports a functional protocol does not automatically support the associated security profiles. And even if it does, implementation details can impair interoperability: certificate formats, role models, algorithms, protocol versions and options must match between manufacturer, integrator and operator.

Legally, IEC 62351 is a voluntary standard. It becomes binding only when laws, regulations, security catalogues or contracts refer to it. Whether and to what extent this is the case in a given country, for a given voltage level or for a given class of installation must be checked case by case. For operators of critical infrastructure, it often serves as a technical reference for the state of the art in protocol security.

Typical misunderstandings

First misunderstanding: IEC 62351 is a switch that can simply be flipped in existing systems. In established control technology landscapes, this is often hindered by old devices, long maintenance cycles, limited computing power, proprietary implementations and strict availability requirements. In addition, there is the change between editions, for example with the fundamentally revised Part 5. It can mean that older and newer implementations do not readily work together. A security function can make sense and still require careful migration planning.

Second misunderstanding: the standard is mainly about encryption. Confidentiality is, however, only one protection dimension. In grid control, authenticity and integrity often matter more. An attacker does not need to be able to read a measured value to cause damage. It may be enough to alter it or to replay an old message. Conversely, a fully encrypted connection remains risky if roles are assigned too coarsely or several people use the same credentials.

Third misunderstanding: conformity with the standard equals security. Standards create common requirements and technical compatibility. They do not, however, eliminate misconfiguration, insecure operating processes or unclear responsibilities. Certificates must be issued, renewed, revoked and checked. Roles must match real tasks. Security events must be evaluated.

Finally, the standard makes visible the tension between security and availability. In office IT, a failed authentication usually only leads to an interruption of work. In grid control technology, the same mechanism, if poorly designed, can prevent access to a plant precisely in the event of a fault, for example when a certificate expires or a revocation list server cannot be reached. This is not an argument for weakening the checks. It does mean, however, that revocation mechanisms, fallback procedures, timing behaviour and emergency roles must be aligned with operational responsibility.

Overall, IEC 62351 governs a specific part of the digital infrastructure of the power system: trustworthy communication between technical and organisational actors. On its own, it does not guarantee secure grid operation. It does, however, create a prerequisite for measured values, control commands, models and access rights to be used dependably in networked control technology landscapes.

Sources

Related glossary entries

Edited by eCMS on 28.11.2026 12:01

© 2026 Erik Schmidt. All rights reserved. Quotations with a link to the source are welcome.