Islanded operation

Islanded operation is the operation of a power grid, a grid section or a microgrid without an electrical connection to the higher-level interconnected grid. In this state, generation and consumption within the island must be balanced at all times. Frequency, voltage, protection and grid stability are then no longer supported by the large interconnected grid. They must be established locally.

In the continental European interconnected grid, the nominal frequency is 50 hertz. The grid frequency shows whether generation and consumption are balanced across the entire synchronously interconnected area. If power is lacking, the frequency falls. If too much is fed in, it rises. In the large interconnected system, deviations are spread across a very large number of power plants, consumers, storage units and control areas. In an island, the same deviations have a much more direct effect, because rotating inertia, short-circuit power and balancing options are smaller. A motor starting up, a photovoltaic system suddenly dropping out or a battery system beginning to charge changes the operating variables much more strongly than in interconnected operation. An analogy: a rower who stands up makes a rowing boat sway, but hardly affects a container ship.

The term islanded operation describes an operating state and not automatically a particular installation. An island grid is operated independently, permanently or regularly, for example on a geographical island or in a remote area. A microgrid can run in interconnected operation and switch to islanded operation when needed. An emergency power system supplies selected consumers during a grid outage, but does not necessarily form a full local grid. Likewise, a battery storage system or a photovoltaic system is not capable of islanded operation merely because it can store or generate electricity. Islanded operation requires a control system that actively sets and stably maintains voltage and frequency.

Frequency, voltage and the role of grid-forming technology

In the interconnected grid, many installations follow an existing grid voltage. They feed in as long as a stable reference is present. Such installations are called grid-following. Many inverters of photovoltaic systems and battery storage systems work this way. They do supply power, but without additional functions they do not form a stable island.

Islanded operation requires installations that provide an electrical reference. These can be grid-forming converters, appropriately designed battery systems or synchronous generators with suitable control, for example in hydropower plants, combined heat and power units or diesel generator sets. In the interconnected grid this task is hardly noticeable, because the totality of synchronous machines and control mechanisms carries it. In small islands it is particularly demanding. In simplified terms: the active power balance mainly determines the frequency, while reactive power is decisive for voltage maintenance. In low-voltage grids with a high resistive line share, the two quantities are more strongly coupled. Both must be controlled without the control loops amplifying each other.

Grid protection also takes on a different significance. In the interconnected grid, short circuits produce high fault currents. Protection devices detect faults from these currents and disconnect the affected lines or installations. In an island with many inverters, short-circuit currents are often lower, because power electronics typically limit the current to little more than the rated current. A protection concept that works in interconnected operation can be too slow, too sensitive or ineffective in islanded operation. Islanded operation is therefore not purely a generation topic. It also concerns grid planning, protection settings, control technology, measurement and operational responsibilities.

Planned and unplanned islanded operation

Planned islanded operation is prepared technically, for example in microgrids, industrial sites, hospitals, data centres, military properties, research grids or remote supply areas. It is specified which consumers are supplied, which generators may start, which loads can be disconnected by load shedding and how the island is resynchronised with the interconnected grid. For this resynchronisation, the frequency, voltage magnitude and phase angle of the island must match the grid side. If connection is made in an uncontrolled way, equipment can be damaged and protective trips can be triggered.

Unplanned islanded operation arises when a grid section is separated from the interconnected grid and local generation keeps running. This endangers above all personnel, because lines then remain energised although they are switched off from the point of view of the upstream grid. Unintended back-feeding can be life-threatening during work on the grid. Decentralised generation installations therefore have islanding detection devices. They disconnect automatically in the event of a grid outage if no specifically designed islanded operation is provided for. Some regard this protection function as an obstacle to local resilience. Its purpose, however, is first of all the safety of persons and equipment and an orderly reconnection.

An installation that switches off during a grid outage is therefore not defective if it was built for normal parallel operation. It fulfils exactly the connection rule that is meant to prevent unplanned islands. If the same installation is to contribute to supply during a fault, it needs other technical properties, a different protection concept and clear operating rules. Resilience therefore does not arise from the mere number of local generators.

Legal and normative framework

In the EU, Regulation (EU) 2016/631 (the network code Requirements for Generators, RfG for short) governs the connection requirements for power-generating facilities. For type C facilities, that is, larger facilities with a connection point below 110 kV and a maximum capacity at or above a threshold set by the transmission system operator, Article 15 requires the capability to take part in islanded operation. However, this obligation exists only if the relevant system operator requires it in coordination with the transmission system operator. Frequency and voltage limits for islanded operation follow the general limit values of the Regulation. In addition, it should be possible to detect the transition from interconnected to islanded operation without relying solely on switch signals. Further requirements concern reduction to house load and fast resynchronisation. This is important for grid restoration.

For small installations on the German low-voltage grid, such as PV systems, storage systems or micro-CHP units, the application rule VDE-AR-N 4105 of VDE FNN applies. It requires a certified grid and system protection (NA protection) with islanding detection. This function can be implemented centrally or integrated in the generating units. From a total capacity of more than 30 kVA at the connection point, a central NA protection is in principle required. According to manufacturer certificates for the 2018-11 version, an island must be detected and the installation switched off within 2 seconds. With dynamic grid support, it can take longer than 2 seconds. Backup power systems that supply buildings during a grid outage must be safely disconnected from the public grid so that nothing can be fed back. The specific requirements depend on the version, voltage level and type of installation. For medium voltage, for example, VDE-AR-N 4110 applies.

Distinction from black start and emergency power

Islanded operation is often confused with black start capability. An installation or system is black-start capable if it can start up and provide voltage without an external power supply. This can be a prerequisite for islanded operation, but it is not the same thing. A generator set can be black-start capable and still supply only individual consumers. Conversely, an island grid can be stable in ongoing operation without every individual generation installation being black-start capable.

Emergency power is also more narrowly defined. In electrical engineering, a further distinction is made between safety power supply, for example for emergency lighting, and standby power supply for other consumers. Such systems supply prioritised consumers such as medical devices, pumps or controls. They are usually designed for a limited time, defined loads and specific changeover processes. Islanded operation of a grid section can reach much further and include several types of generation, storage, controllable loads and distribution grids. It is then not just a matter of switching on a standby generator, but of complete local grid operation with ongoing power balancing and stability management.

Self-sufficiency is likewise not an exact substitute term. A building or district can generate over the year as much electricity as it consumes. That says little about whether it can be supplied at every point in time without the interconnected grid. Islanded operation requires generation and load to be balanced simultaneously. Annual balances, self-consumption rates or calculated degrees of self-sufficiency often obscure this time requirement.

Why islanded operation matters for resilience

Islanded operation can improve supply during disruptions if it is deliberately planned and integrated into grid operation. In widespread outages, local islands can supply critical infrastructure or support grid restoration. The RfG expressly provides that several generation installations within an island can be operated in parallel. In rural distribution grids, on islands or in industrial sites, a prepared microgrid can shorten outage times. For hospitals, waterworks, telecommunications or cooling, this capability can be more important than the cost of individual kilowatt-hours.

The economic assessment nevertheless remains difficult. Islanded-operation capability costs money for converters, storage, control, protection technology, testing, personnel and maintenance, and it does so for capabilities that are rarely used. The benefit lies in avoided damage, operational continuity and support for grid restoration. Markets often remunerate such properties only incompletely, because they cannot easily be assigned to a kilowatt-hour. Local stability thus becomes a question of ancillary services: who pays for it if it has value mainly in exceptional cases?

Islanded operation is also demanding organisationally. The distribution system operator is responsible for safe grid operation. Installation operators often optimise for self-consumption, electricity price or the availability of their processes. For municipalities and operators of critical infrastructure, security of supply is the concern. These goals can fit together, but they must be organised technically and contractually. Without clear responsibility for switching operations, protection limits, load shedding and reconnection, a local island can itself become a source of disturbance during a fault.

Typical misunderstandings

  • Decentralised generation does not automatically make a grid failure-proof. Photovoltaic systems on many roofs increase local generation. They secure islanded operation only if inverters, storage and protection technology are designed for it. Standard installations switch off during a grid outage. This does not contradict the energy transition, but follows from the connection rules for safe parallel operation.

  • A storage unit alone is not enough. A battery storage system can provide energy and regulate very quickly. For islanded operation, however, it must work in a grid-forming way, have enough power for load steps, store enough energy for the bridging duration and be coordinated with other generators. Capacity in kilowatt-hours is not sufficient as a specification. Equally important are the power in kilowatts, the control behaviour, the overload capability, the black-start capability and the integration into the protection concept.

  • Climate protection and crisis resilience are not the same thing. Renewable energies can facilitate islanded operation if they are combined with storage, controllable loads and suitable grid technology. An island with a lot of photovoltaics, however, needs different reserves for evening hours, changing cloud cover and longer dark periods than a grid with constantly available generators. What matters is which combination of installations, control and load management enables stable supply for the defined purpose.

Islanded operation shows what the interconnected grid constantly provides in normal operation: it supplies the frequency reference, maintains voltage, provides fault current, balances between regions, holds reserve power and coordinates protection responses. Anyone planning islanded operation must replace these functions locally or limit the scope of supply. The term therefore does not stand for romantic independence from the grid, but for a demanding operating state with clear technical limits, costs and responsibilities. Used precisely, it allows local resilience to be distinguished from mere local power generation.