Inertia Constant (Trägheitskonstante)
The inertia constant, in German usually called Trägheitskonstante, indicates how much kinetic energy is stored in the rotating masses of an electrical machine at rated speed, relative to its rated power. It is usually denoted by H and expressed in seconds. Formally, H = E_kin / S_n. Here, E_kin = ½ · J · ω² is the rotational energy, with the moment of inertia J and the rated angular velocity ω. S_n is the rated apparent power in megavolt-amperes (MVA). Some sets of rules relate H instead to the active power in megawatts (MW). A numerical value is therefore only comparable when the reference quantity is stated.
A worked example: a synchronous generator with 500 MVA and H = 5 s stores about 500 MVA · 5 s = 2,500 MWs, i.e. roughly 2,500 megajoules. This energy resides in the turbine, the generator rotor and the mechanically coupled masses. In the event of a frequency deviation, it is released or absorbed without any measurement or control decision. The reason is the physical coupling between the machine's rotational speed and the electrical grid frequency.
What the unit seconds means and what it does not
In the technical literature, H is often illustrated as follows: it is the time in which the machine could deliver its rated power solely from its stored rotational energy. This is a computational interpretation and not an operating time. In the grid, only a small part of this energy can be used, because the frequency may deviate only slightly from 50 hertz. If the speed falls from 50 to 49 Hz, only about 4 percent of the stored energy is released, because energy grows with the square of the speed. In the example, that would be just under 100 MJ instead of 2,500 MJ. H is therefore above all a ratio of energy to power. It is not suitable as an indication of how long a machine can continue to supply power after a disturbance.
Equation of motion and rate of change of frequency
In a 50-hertz alternating-current system, synchronous machines rotate at a speed that is rigidly tied to the grid frequency. If more electrical power is drawn than is supplied mechanically, the grid extracts energy from the rotating masses. The rotors slow down, and the frequency falls. In the case of a surplus of generation, they accelerate, and the frequency rises. This is described by the equation of motion of the synchronous machine, the swing equation. Simplified in per-unit quantities, it reads: (2H / f0) · df/dt = (P_mech − P_el) / S_n.
From this follows the initial rate of change of frequency (RoCoF) directly after a disturbance. It is proportional to the power imbalance and inversely proportional to the inertia. A simplified example with a single equivalent generator: if 10 percent of the power is lost abruptly and H = 5 s, the frequency initially falls by about 0.1 · 50 Hz / (2 · 5 s) = 0.5 Hz per second. With half the inertia, it would be about 1 Hz per second. Real grids behave in a more complicated way. Loads also respond to frequency, and the frequency can differ regionally for short periods. The basic relationship remains the same, however: more stored rotational energy means a slower frequency trajectory.
From the machine to the system
The inertia constant of an individual machine must be distinguished from system inertia. For the power system, what counts is the sum of the rotational energies of all machines currently coupled synchronously to the grid. Dividing this sum by the summed rated power yields an equivalent system inertia constant. A small generator with a high H therefore contributes little. A large unit with a medium H can be more significant. The operating state is decisive: a power plant that is not synchronously connected to the grid provides no inertia. Transmission system operators therefore estimate system inertia hourly or continuously. They use data on power plant dispatch, H values and rated powers, or evaluate measured frequency events.
Frequently cited orders of magnitude for H are about 3 to 9 s for thermal turbine sets and about 2 to 4 s for hydropower generators. The values depend on design, speed and reference power. They should therefore be understood only as guidance and do not replace manufacturer data.
The inertia constant is also not the same as the mechanical moment of inertia J. J describes the mass and geometry of the rotor in kg·m². H translates this property into a quantity that is comparable in grid engineering by relating the stored energy to the rated electrical power. German sets of rules frequently use the starting time constant T_A. It equals twice H, provided both are related to the same power. Stored energy and instantaneous reserve then result as ½ · T_A · P_N.
Distinction from power, balancing power and instantaneous reserve
Power is an instantaneous rate of energy transfer in megawatts. The inertia constant, by contrast, describes an energy store in relation to power. Nor should it be equated with balancing power. Frequency Containment Reserve and subsequent reserves are measured, activated and controlled. Inertia acts earlier, namely in the first fractions of a second to seconds after a disturbance. Only after that do turbine governors, batteries or flexible consumers take full effect. The effect of the rotating masses, which occurs without delay and without a control decision, is called instantaneous reserve in Germany.
Significance for frequency maintenance and grid operation
The grid frequency shows directly whether generation and consumption are in balance. If a large power plant unit or an important line fails, a power step occurs. Inertia does not reduce the magnitude of this loss and does not bring the frequency back permanently. It does, however, slow down the trajectory. This leaves time until control reserves take effect. In addition, frequency gradients remain within ranges that protection devices and generation plants can handle. If the gradients are too steep, protection relays can trip, plants can disconnect from the grid and follow-on outages can be facilitated.
Why the concept is becoming more important with renewable generation
In power systems with many thermal power plants and large hydropower plants, inertia long arose as a by-product of generation via synchronous machines. Photovoltaic plants, battery storage systems and most modern wind turbines, by contrast, feed in via inverters. These decouple the feed-in from rotating masses. Grid-following inverters provide no inherent inertial response without special control. A system can therefore have enough megawatts to cover consumption and still have little natural inertia. This applies especially in hours with a lot of wind and solar power, little conventional generation and high imports via direct-current links.
There are several technical solutions for this. Grid-forming converters behave toward the grid like a voltage source. They can provide an undelayed, inertia-like response, which is also referred to as synthetic inertia. For this they need an energy store and reserves in terms of power and current. Synchronous condensers, also called phase shifters, and additional flywheels provide genuine rotating inertia and at the same time short-circuit power, without generating energy themselves. Fast frequency support through measured and activated control, for example Fast Frequency Response, acts similarly but sets in with a certain delay. It is therefore not the same as inherent inertia.
Legal framework in Germany
In Germany, instantaneous reserve is part of the non-frequency-related ancillary service "inertia for local grid stability" under § 12h EnWG (German Energy Industry Act). In December 2020, the Bundesnetzagentur (Federal Network Agency) had still exempted it from market-based procurement. With determination BK6-23-010 of 22 April 2025, it lifted this exemption and established a fixed-price system. The procurement concept applies until 31 December 2031. The four transmission system operators started procurement on 22 January 2026. The first preview period runs until 21 January 2028.
-
The quantity is stated in MWs and calculated from rated active power and starting time constant. The quantity relevant for remuneration is ½ · m · T_AN · P_N, where m is the marketed share of the unit.
-
There are four products: positive and negative instantaneous reserve, each either as a basic product with at least 30 percent availability or as a premium product with at least 90 percent. The service must be provided without delay, and the capability to do so must not be deactivatable.
-
Inertia that synchronous machines provide anyway while generating active power is not remunerated. Eligible for remuneration are, for example, additional flywheels, phase-shifter operation and grid-forming converters whose grid-forming properties have been demonstrated in accordance with the VDE FNN guideline.
-
For the first fixed-price period, the transmission system operators state base prices of 805 euros per MWs and year for the premium product and 76 euros per MWs and year for the basic product, in each case plus an availability-dependent component. The fixed prices can be adjusted in coordination with the Bundesnetzagentur.
Typical misinterpretations
Inertia is not a general safety reserve in the sense of additional energy generation. It bridges the beginning of a disturbance but does not restore the balance of the power budget. If control reserves are lacking afterwards, the frequency continues to fall despite high inertia, only more slowly. Equally shortened is the conclusion that fewer conventional power plants automatically mean less security of supply. The narrower finding is what is substantiated: with fewer synchronously coupled machines, natural system inertia decreases, as long as no other plants take over this task. It follows that stability must be specified technically, taken into account in grid operation and, where needed, procured via connection rules or markets. In Germany, this is now happening.
A single H value can also be misleading. Its contribution to the system depends on the rated power, the reference quantity (MVA or MW) and on whether the machine is currently synchronized. For system analyses, what counts is the effective inertia actually present in the respective grid area at the respective time. It is increasingly also considered regionally, because after grid splits individual sub-grids can be equipped very differently.
Sources
- Marktgestützte Beschaffung von Momentanreserve — Deutsche Übertragungsnetzbetreiber (netztransparenz.de); unbekannt (Stand der Dokumente bis Oktober 2026). Abschnitte Einleitung, Was ist Momentanreserve?, Regulatorischer Rahmen, Festpreise
- Konzept für die Spezifikationen und technischen Anforderungen der marktgestützten Beschaffung der Momentanreserve gemäß § 12h Abs. 1 S. 1 Nr. 2, Abs. 5 EnWG (BK6-23-010) — Bundesnetzagentur; 2025-04-22. Abschnitte A.I–II, B.III, B.XI, C.I Nr. 1 und 8, D.II, H.VI
- Inertia and Rate of Change of Frequency (RoCoF) — ENTSO-E; unbekannt. Kapitel 3 und 4 (Definition Systemträgheit, RoCoF, Trägheitsschätzung)
- Electric Power System Inertia: Requirements, Challenges and Solutions — Technical University of Denmark (DTU Orbit), Review-Artikel; unbekannt. Abschnitt zur Definition von H und Übersicht typischer H-Werte nach Erzeugungsart
- Future System Inertia — ENTSO-E (Nordic TSOs); unbekannt. Kapitel 2 (Definitionen, Bewegungsgleichung) und Kapitel 4 (kinetische Energie je Land)
Related glossary entries
- rate of change of frequency (RoCoF)
- system inertia
- balancing power
- Frequency Containment Reserve
- instantaneous reserve
- grid frequency
- inverters
- Grid-forming converters
- synthetic inertia
- ancillary service
- transmission system operators