Brownout

A brownout is a temporary reduction of the electrical voltage in a power grid or in part of it. The supply does not fail completely. However, electrical devices only operate in a limited or unreliable way. The term comes from English and describes the image of incandescent lamps glowing dimmer and slightly brownish as the voltage drops. Technically, it is not about "too little electricity" in a general sense. It means that the voltage at a point in the grid deviates from its intended range. The term is used mainly in North American and everyday usage. It covers both unintended undervoltages and a deliberately ordered voltage reduction by which a grid operator curbs consumption in an emergency.

Voltage limits and legal framework in Germany

In the German low-voltage grid, the voltage at the end of the grid connection is, according to the Low-Voltage Connection Ordinance (Niederspannungsanschlussverordnung, NAV), about 230 volts between a line conductor and the neutral conductor, or about 400 volts between two line conductors, at a frequency of about 50 hertz. Section 16(3) NAV obliges the grid operator to keep voltage and frequency as constant as possible, so that commonly used consumer devices and generation installations can operate without problems. Anyone who places higher demands on power quality, for example a business with sensitive production technology, must, under the same provision, take precautions of their own within their area. The NAV applies only to low-voltage connections. For medium- and high-voltage customers, grid connection contracts and technical connection rules govern the details.

Concrete figures are given by the European standard EN 50160, which applies in Germany as DIN EN 50160. It describes the characteristics of the supply voltage at the point of delivery in public grids. For low voltage, under normal operating conditions: 95 percent of the ten-minute mean values of the rms value over one week must lie within plus or minus 10 percent of the nominal voltage, i.e. roughly between 207 and 253 volts. For the remaining values and for special cases such as remote or non-interconnected grids, the standard specifies a wider band downward to minus 15 percent. It should be noted that the standard describes statistical characteristics under normal operating conditions. It is not a law, and it does not guarantee an absolute limit for every single second. A brief dip that disappears in the ten-minute average can still disturb devices.

In everyday usage, a brownout usually refers to a longer perceptible undervoltage or a controlled voltage reduction. In German regulation and grid operation, however, it is not a firmly defined technical term. More clearly delimited there are terms such as voltage dip, slow voltage variation, undervoltage and supply interruption.

Distinction from voltage dip, supply interruption, load shedding and blackout

A brownout differs from a voltage dip primarily in its duration. According to DIN EN 50160, a voltage dip occurs when the rms value falls below 90 percent of the reference voltage. By definition it lasts between 10 milliseconds and one minute. Typical causes are short circuits, switching operations or the start-up of large motors. A brownout, by contrast, is more likely to refer to an undervoltage lasting minutes or hours. In the media and in political debates this distinction is often blurred. This easily creates the impression that every disturbance of power quality is already the precursor of a large-scale outage. For assessing security of supply, this equation is of no help.

In a supply interruption, the voltage at the connection falls practically to zero. In a brownout, by contrast, it remains present, only too low. A blackout is a large-scale total outage because parts of the grid shut down or can no longer be kept stable. For consumers, both can have serious consequences. The physical disturbance, however, is a different one.

Load shedding is not the same thing either. In load shedding, certain consumers or grid areas are deliberately disconnected from the grid in order to stabilise the rest of the system. This happens either automatically through protection technology, for example frequency-dependent, or according to operational plans. A deliberate brownout can be a milder form of consumption reduction, because at lower voltage the power consumption of some devices decreases. However, no customers are disconnected from the grid. How strong the effect is depends on which devices are connected.

Why voltage does not automatically mean supply

Power supply is often described as a question of sufficient quantities of energy. For the operation of an alternating-current grid, this view is not sufficient. The grid must at all times keep frequency, voltage, current flows and the loading of equipment within permissible limits. The frequency indicates whether generation and consumption are in balance across the entire synchronous interconnected grid. It is almost the same everywhere. Voltage, by contrast, is a local quantity. It depends, among other things, on line lengths, loads, feed-in, reactive power, transformers and grid control. A house at the end of a long rural low-voltage feeder can have considerably less voltage than one directly next to the local distribution transformer.

A grid can be adequately supplied overall and still have voltage problems locally. Conversely, firm capacity can be lacking in the overall system without an undervoltage initially becoming visible. This distinction is also important for responsibilities. Transmission system operators secure the balance in the extra-high-voltage grid, coordinate ancillary services and are responsible for system operation. Distribution system operators, at regional and local level, maintain among other things the voltage bands, plan grid expansion and operate transformers, switchgear and protection technology. A brownout therefore says nothing on its own about whether there is too little power plant capacity overall. Possible causes are local overload, inadequate voltage regulation, missing reactive power, faulty equipment, extreme load situations or a deliberately initiated reduction. Anyone who wants to find the cause must consider grid level, duration, load situation and operating state.

Technical effect on consumers and grid operation

Electrical devices react differently to undervoltage. For resistive loads such as resistance heaters or classic incandescent lamps, the power falls roughly with the square of the voltage. Ten percent less voltage here means about 19 percent less power. The lamp becomes visibly darker, the heater delivers less heat. Electric motors at too low a voltage under load often draw more current, heat up more or no longer start reliably. Electronic power supplies often keep their output power constant and therefore draw more current as the input voltage falls, as long as their regulation allows it. If the voltage falls further, they switch off or behave unstably.

For households, a brownout therefore does not appear uniformly. Some devices seem to run normally, others flicker, hum, restart or fail. For industry, commerce, data centres, hospitals and transport infrastructure, even brief deviations in voltage quality can be relevant. Production processes, controls, pumps, cooling systems and drives are often more sensitive than simple household appliances. Many critical installations therefore use uninterruptible power supplies, voltage conditioners, protective relays with undervoltage tripping or their own backup power systems. This fits the logic of Section 16 NAV, under which increased quality requirements lie within the responsibility of the connection user.

In grid operation, undervoltage is not just a comfort problem. If the voltage falls and constant-power loads therefore draw more current, the current loading and the losses in lines and transformers rise locally. Protection systems can trip. In unfavourable cases the disturbance intensifies itself, because the behaviour of the connected devices pushes the voltage down further. In the extreme case, a voltage collapse threatens. Brownouts are therefore not regarded as a normal operating state. They are a deviation that must be avoided, limited or strictly controlled.

Controlled voltage reduction and its limits

In some power systems, above all in North America, the voltage is deliberately lowered to reduce consumption. The term Conservation Voltage Reduction (CVR) is commonly used for this. The idea: if the voltage is lowered slightly within the permissible band, the power drawn by voltage-dependent consumers falls. A study by the Pacific Northwest National Laboratory for the US Department of Energy found, depending on the feeder, savings in annual energy and peak load of about 0.5 to 4 percent. Extrapolated to all US distribution feeders, this amounted to about 3 percent of annual consumption. Almost all of the saving arose at the end consumers. According to the study, lower grid losses played hardly any role.

This effect is limited and not the same for all consumers. Modern electronic devices, regulated motors and other constant-power loads weaken the effect. With thermostat-controlled devices, consumption often merely shifts in time, because heating or cooling subsequently runs longer. In addition, the voltage must not fall below the permissible limits. Otherwise malfunctions and damage to devices threaten, and the grid operator breaches its quality obligations. Study results from North America, where different nominal voltages and tolerances apply, cannot simply be transferred to Germany.

A controlled voltage reduction therefore replaces neither firm capacity nor grid expansion, storage, flexibility or a functioning system operation. In certain situations it can be an aid, but it remains bound by narrow technical limits. In Germany, brownout is not a customary official operational term for this. More common are categories such as voltage regulation, voltage quality, congestion management, load management or emergency measures.

Misunderstandings in the debate on security of supply

In public debates, brownout is often used as a dramatic intermediate stage between stable supply and blackout. This creates more uncertainty than clarity if it remains unclear what is meant: a local undervoltage, a planned consumption reduction, rotating shutdowns or a general electricity shortage situation. Each of these situations has different causes, responsibilities and countermeasures.

A common mistake is to derive brownouts directly from the share of renewable energy. Renewable feed-in does change the requirements for grid operation, voltage maintenance and ancillary services. However, photovoltaics in distribution grids tends to lead to local overvoltage. High loads without sufficient grid infrastructure, by contrast, favour undervoltage. Inverters of modern installations can also themselves provide reactive power and thus support the voltage. A higher brownout risk therefore does not follow automatically. What is decisive is whether grid planning, equipment, voltage regulation, reactive power provision and controllability fit the respective feed-in and consumption structure.

Equating brownout with electricity scarcity is equally imprecise. Electricity scarcity is about whether demand and generation can be balanced at all times. A brownout concerns the voltage at particular grid nodes or in particular grid areas. Both problems can occur together, but do not have to. Remedies for electricity scarcity, such as additional generation or consumption reduction, do not automatically solve local voltage problems. Conversely, remedies for voltage problems do not replace securing the power balance. These include, for example, regulated local distribution transformers, reactive power management or grid expansion.

Role in an electrified power system

With heat pumps, electromobility, battery storage, photovoltaic systems and new industrial electricity applications, the loading of many distribution grids is changing. The additional consumption is distributed neither evenly over the day nor evenly across the grid. Charging points, electric heating and decentralised feed-in change the voltage profiles in the low- and medium-voltage grid. On a cold winter evening, many heat pumps and charging sessions can coincide in one street. At the end of long lines, the voltage then drops noticeably if the grid is not designed for this or is not controlled.

This does not argue against electrification. It does show, however, that new consumers and feed-in sources must be integrated in a grid-serving manner. Voltage problems can be reduced, among other things, by:

  • regulated local distribution transformers that adjust their transformation ratio under load,

  • smart metering systems and grid state monitoring in the low-voltage grid,

  • controllable consumption devices and grid-oriented load management,

  • reactive power control of inverters and voltage regulation in medium and low voltage,

  • forward-looking grid planning, targeted grid reinforcement and transparent connection rules.

Economically, this is about the distribution of costs and incentives: Who may feed in or charge, and when? Who pays for grid reinforcement? Which flexibility is remunerated? And which interventions are permissible in the event of congestion?

A brownout thus does not stand for a general weakness of the power system. It denotes a concrete violation of voltage quality or its deliberate use. The term becomes precise only when it is separated from voltage dip, blackout, load shedding, frequency disturbance and electricity shortage situation. It makes visible that security of supply depends not only on kilowatt-hours generated. It also matters that electrical energy is delivered to the consumers' connection with permissible voltage, sufficient quality and clearly regulated responsibility.