Seasonal performance factor (Jahresarbeitszahl, JAZ)

The Jahresarbeitszahl, JAZ for short, describes how much useful heat a heat pump provides within one year in relation to the electrical energy used for it. A Jahresarbeitszahl of 4 means: calculated over the year, one kilowatt hour of electricity yields four kilowatt hours of heat for space heating or hot water. Three of these kilowatt hours then do not come from the power grid but from ambient heat, that is, from air, ground, groundwater or waste heat. In the English-speaking world it largely corresponds to the seasonal performance factor.

The Jahresarbeitszahl is not a power rating but a ratio of energy quantities over a period of time. The numerator is the heat delivered in kilowatt hours thermal, the denominator the electricity consumption used in kilowatt hours electric. Because both quantities are measured in kilowatt hours, the metric is formally dimensionless. In substance, however, the distinction between heat and electricity remains central, because the heat pump does not create energy out of nothing. With the help of electricity, it lifts existing ambient heat to a higher, usable temperature level.

Distinction from COP, SCOP and efficiency

The Jahresarbeitszahl is often confused with the COP. The COP (coefficient of performance) is the ratio of heat output to electrical power input at a specific operating point. A common test point for air-to-water heat pumps is, for example, an air temperature of 7 degrees Celsius at a flow temperature of 35 degrees Celsius. The COP is thus a snapshot under precisely defined laboratory conditions.

The SCOP (seasonal coefficient of performance) lies in between. It weights several test points according to a standardised climate and load profile to give a seasonal value. This allows devices to be compared under the same assumptions, but the SCOP does not reflect a specific building. The Jahresarbeitszahl, by contrast, summarises real operation: mild autumn days, cold winter hours, hot water production, defrost cycles, part load, cycling and, where applicable, the electric backup heater. A device with a good COP on the data sheet may therefore achieve only a mediocre Jahresarbeitszahl in practice, for example because of excessively high flow temperatures or poorly set controls.

Another difference between planning and measurement is important. Before installation, the Jahresarbeitszahl can only be calculated, in Germany usually according to guideline VDI 4650 Part 1. This calculation works with manufacturer data, a reference climate and the planned heating circuit temperatures. It is a forecast. The Jahresarbeitszahl actually achieved is only determined after a year of operation, measured with a heat meter and an electricity meter.

The Jahresarbeitszahl should be described as an efficiency only with caution. In a boiler, the heat is limited by the energy content of the fuel. When condensing boilers reach values above 100 percent, this is only due to the reference quantity, the net calorific value. A heat pump, by contrast, uses electricity as drive energy and additionally taps ambient heat. A Jahresarbeitszahl above 1 therefore violates no physical principle. It shows how effectively the system uses electricity to make existing heat usable.

Which system boundary counts

How meaningful a Jahresarbeitszahl is depends strongly on which electricity consumption and heat quantities are included. A narrow system boundary considers only the heat pump unit. A wider boundary also includes circulation pumps, controls, fans, brine pumps, defrost energy and the electric backup heater. For assessing a heating system, the broader boundary is usually more sensible, because these consumptions appear on the electricity bill and must be covered in the power system. Standardised methods also define such boundaries explicitly. For example, VDI 4650 Part 1 accounts for hot water production at the condenser of the heat pump and leaves out the electricity of charging and circulation pumps. Anyone comparing values from different sources should therefore always ask which system boundary was chosen.

The delimitation also matters on the heat side: is only space heating considered, or hot water as well? Hot water requires higher temperatures than a well-designed heating system, so efficiency falls as a result. In the Fraunhofer ISE field measurement, around 19 percent of the heat delivered went to domestic hot water heating. In some of the systems with combination storage tanks, the temperature levels for heating and hot water were not cleanly separated, so heat was unnecessarily provided at hot water temperature.

For systems with an electric backup heater, it must be disclosed whether its electricity is included in the metric. An electric backup heater has a performance factor of about 1: it converts electricity almost completely into heat but uses no ambient heat. If it runs frequently, the Jahresarbeitszahl falls markedly. If it is left out of the measurement, the system looks better than it actually is in terms of electricity consumption, costs and grid load.

Measured values in practice

Reliable practical values for Germany are provided by field measurements of Fraunhofer ISE. In the project WP-QS im Bestand (heat pumps in existing buildings), 77 heat pumps in one- to three-family houses built between 1826 and 2001 were measured over four years. The 61 air-to-water heat pumps achieved an average Jahresarbeitszahl of 3.4, with a range of 2.6 to 4.9. The 16 ground-coupled systems reached an average of 4.3, with a range of 3.6 to 5.4. In the predecessor project with measurement year 2018/19, the averages had still been 3.1 and 4.1.

The study found no correlation between year of construction and efficiency. Sufficiently large radiators could on average be operated at similarly low temperatures as underfloor or surface heating systems. The electric backup heaters supplied only around 1.3 percent of the electrical work in the air-to-water heat pumps. The institute attributes this partly to comparatively mild winters during the measurement period. In harsher winters, the backup heater share may be higher and the Jahresarbeitszahlen lower. Such measured values apply only to the respective sample and system boundary and are not an average of all systems in Germany.

Technical influencing factors

The most important technical influencing factor is the temperature lift, that is, the temperature difference between the heat source and the heating system. The warmer the source and the lower the required flow temperature, the less electrical work the compressor has to perform. In winter, ground and groundwater usually provide more stable source temperatures than outdoor air. Brine-to-water and water-to-water heat pumps therefore achieve higher Jahresarbeitszahlen on average. A fixed ranking for every building does not follow from this, because investment costs, the plot, permits and system design also play a part.

On the building side, heating surfaces, insulation standard and hydraulic balancing determine how high the flow temperature must be. Small radiators in unrenovated rooms force higher temperatures and lower the performance factor. Controls also play a role: an unnecessarily steep heating curve, frequent switching on and off (cycling) or poorly matched storage tanks worsen efficiency. In the Fraunhofer field test, many heat pumps were oversized relative to consumption, and some systems cycled very frequently.

With air-to-water heat pumps, defrost cycles are added. If ice forms on the evaporator, the system must remove it with additional energy in the defrost cycle. This is technically necessary but lowers the Jahresarbeitszahl. Such operating effects explain why measured values can deviate from brochure figures without the device being defective.

Significance for the power system

With the electrification of heat supply, part of the energy demand shifts from oil, gas or biomass to the electricity sector. How much this burdens the power system depends substantially on the Jahresarbeitszahl. One million heat pumps with a Jahresarbeitszahl of 4 need around 37 percent less electricity for the same quantity of heat than one million systems with a Jahresarbeitszahl of 2.5.

For generation, the energy quantity over the year counts. For grids and security of supply, it also matters when the electricity is needed. Heat pumps run mainly in cold weather. Then heat demand is high, the efficiency of air-source heat pumps falls and their electrical power consumption rises. A good Jahresarbeitszahl therefore says nothing about how high the simultaneous load is on a cold winter evening. Grid capacity is dimensioned according to this peak load. For grid operators, connection capacity, controllability, the local concentration of heat pumps and typical load profiles therefore count. The Jahresarbeitszahl complements this analysis with an indication of efficiency but does not replace it.

The Jahresarbeitszahl is thus linked to residual load and flexibility. A well-insulated building with low flow temperatures and thermal storage mass can temporarily shift operation without comfort suffering immediately. A poorly renovated building with tight sizing leaves less leeway during cold spells. The Jahresarbeitszahl describes efficiency over the year, not the flexibility available in a particular hour.

Economic significance and significance under funding law

For households, the Jahresarbeitszahl translates directly into running costs: the higher it is, the less electricity is needed for the same quantity of heat. Whether a heat pump is cheaper than a gas heating system, however, also depends on electricity and gas prices, grid charges, CO₂ costs, investment and maintenance.

In Germany, the metric is also used in funding. For the Federal Funding for Efficient Buildings in the form of individual measures (BEG EM, application at KfW), according to the presentation by Gebäudeforum klimaneutral, a design for a Jahresarbeitszahl of at least 3.0 is required. Proof is calculated in advance according to VDI 4650 Part 1; among other things, hydraulic balancing and a heating curve adapted to the building are also required. What is funded is thus a calculated, not a measured efficiency. Whether the system later reaches the value in operation depends on installation, adjustment, weather and use. Funding conditions change frequently; the applicable version of the guideline is decisive in each case.

Typical misinterpretations

  • A high Jahresarbeitszahl makes heat pumps automatically climate-neutral: the metric contains no information about the electricity mix. How much CO₂ a heat pump saves depends on how and when its electricity is generated. For the measured pool of systems in 2024, using quarter-hourly emission factors, Fraunhofer ISE calculated around 64 percent less CO₂ than with natural gas heating. Using annual average values of the electricity mix, the result was 68 percent.

  • Final energy equals overall assessment: with a Jahresarbeitszahl of 4, about 10,000 kilowatt hours of gas are set against around 2,500 kilowatt hours of electricity. For the calculation within the building, this is meaningful. On its own, however, this comparison says nothing about primary energy, emissions, infrastructure costs or import dependence. It also assumes, in simplified form, that the boiler converts the gas energy into heat almost without loss.

  • An average replaces operating quality: two systems can have the same Jahresarbeitszahl and still burden the grid differently. One runs steadily at a low flow temperature. The other often uses the electric backup heater on cold days and partly compensates for this in efficient transitional periods.

  • Planned value equals measured value: a Jahresarbeitszahl calculated according to VDI 4650 is a forecast under standard assumptions and not a measurement result.

The Jahresarbeitszahl is thus a central but limited metric. It shows how efficiently a heat pump converts electricity into useful heat in real annual operation. When the electricity is needed, how high the peak load is and how well the system fits into a grid area, it does not explain on its own. It becomes meaningful only together with the device, the building, operation and a clearly stated system boundary.