Frequency nadir
The frequency nadir is the lowest value that the grid frequency reaches after a sudden disturbance. Afterwards it rises again or settles at a new level. In the Continental European interconnected system, the nominal frequency is 50 hertz. Such a disturbance can be the loss of a large power plant unit, an HVDC link or a large import of power. Power is then briefly missing: consumers draw more than is being fed in. The frequency falls until physical inertia, frequency-dependent loads and automatic control slow down and reverse the decline. The lowest point of this curve is the nadir. For overfrequency after a sudden loss of load there is a mirror-image counterpart, the frequency zenith or frequency maximum.
The nadir is not a quantity of energy but a point in a dynamic process. It is stated in hertz, either as an absolute frequency, for example 49.72 Hz, or as a deviation from the setpoint, for example minus 280 mHz. It also matters when it is reached. This usually happens a few seconds after the disturbance and often before primary control has reached its full output. How low and how early the nadir occurs depends on the size of the outage, the system inertia, the behaviour of the loads and the speed of the frequency-supporting responses.
Frequency curve after a disturbance
In an alternating-current system, a power deficit immediately affects the rotational speed of all synchronously coupled generators and thus the frequency. If generation is missing, the rotating masses of generators and turbines release kinetic energy and slow down in the process. This instantaneous reserve is based on the system inertia of the synchronous machines. It does not have to be called upon but acts physically at once, as long as the machines are electrically connected to the grid.
Immediately after the disturbance, the rate of change of frequency is particularly important, in short RoCoF (rate of change of frequency). In simplified terms: the initial frequency gradient is proportional to the relative power deficit and inversely proportional to the system's inertia constant H. A worked example: if one percent of system power is lost and H is five seconds, the frequency initially falls by about 0.05 Hz per second. With half the inertia, it would be twice as fast. However, the nadir does not result from this initial slope alone. It follows from the interplay of disturbance size, inertia, frequency-dependent consumption, primary control and technical response times.
Automatic primary control is called Frequency Containment Reserve, in short FCR, in the European regulatory framework. In the Continental European synchronous area, it is provided in a decentralised way and jointly by all participants. It responds linearly to the deviation from 50.0 Hz, outside a deadband of 49.99 to 50.01 Hz. At a deviation of ±200 mHz, the participating units must provide the entire FCR within 30 seconds. Control therefore starts quickly but only reaches its full effect after some time. This is why the frequency can initially keep falling even though control is ramping up. The nadir is the moment at which inertia, load response and already activated reserve together just balance the deficit.
Distinction from related quantities
The frequency nadir is often confused with other terms of frequency control. The nominal frequency of 50 Hz is the target value. The frequency deviation is the distance from the nominal frequency at a given point in time. RoCoF describes how fast the frequency changes. The quasi-steady-state frequency deviation is the level at which the frequency temporarily settles after the first control response, before secondary control brings it back to 50 Hz. The nadir, by contrast, is the lowest point of the entire initial frequency movement. It therefore always lies below the quasi-steady-state value or at most coincides with it.
The size of the disturbance is likewise not the same as the nadir. An outage of 1,000 megawatts does not automatically lead to a particular frequency value. In a large, inert interconnected system well equipped with FCR, it triggers only a moderate dip. In a smaller grid or one with less inertia, the same outage can cause a considerably lower nadir. The disturbance is the trigger. The nadir shows how well the system absorbs this trigger in the first seconds.
Likewise, the nadir must be distinguished from balancing reserve. Reserve is a means of supporting frequency, whereas the nadir is a result of the frequency curve. A sufficient quantity of reserve only ensures a non-critical nadir if it acts fast enough, is activated reliably and is not restricted by grid bottlenecks or protection functions.
Limits in Continental Europe
In the EU, the Guideline on electricity transmission system operation, Regulation (EU) 2017/1485, governs frequency control. It is also called the System Operation Guideline (SOGL). For Continental Europe, Article 153 sets a reference incident of 3,000 MW in the positive and negative direction. The FCR is sized so that it covers at least this incident. After such an outage, the frequency must remain within the maximum permissible instantaneous frequency deviation. It must also stabilise within the maximum quasi-steady-state deviation.
For Continental Europe, the maximum permissible instantaneous frequency deviation is 800 mHz. Translated into the nadir, this means: after an outage up to the size of the reference incident, the frequency should not fall below 49.2 Hz. Other synchronous areas have their own values. In the Nordic synchronous area, for example, it is 1,000 mHz. According to ENTSO-E studies, lower inertia has so far not been critical for the normative 3,000 MW outage in the interconnected system as long as it remains intact. In the event of a system split such as on 4 November 2006, however, it has a considerable effect.
Significance for protection technology and security of supply
The nadir has practical consequences because protection devices are set to frequency thresholds. The network code on emergency and restoration, Regulation (EU) 2017/2196, provides for automatic under-frequency load shedding in Continental Europe. It begins at 49.0 Hz at the latest and continues in stages down to 48.0 Hz. By then, a total of 45 percent of the load is to have been shed. In Germany, according to the system protection plan, the load-shedding stages lie between 49.0 and 48.1 Hz. Before that, further frequency-dependent measures are foreseen, such as switching off or redirecting pumped-storage power plants in the event of under-frequency.
This makes the safety margin tangible: between the design target of 49.2 Hz and the first load-shedding stage at 49.0 Hz there are only about 200 mHz. A low nadir does not mean that a power outage is imminent. However, it shows that the distance to protection thresholds is shrinking. How large this margin is depends on technical parameters and operational decisions: how much FCR is available and with what dynamics, which large units can fail at the same time, and whether the interconnected system stays intact. Load shedding can prevent a large-scale collapse but itself interrupts the supply to many customers.
Why the term is becoming more important with the energy transition
In a power system with many large generators, a large part of the initial frequency support comes from their rotating masses. Wind and photovoltaic plants as well as battery storage, by contrast, are mostly connected via power electronics. Without special control methods, they do not contribute to inertia on their own. For the same disturbance, the frequency can then fall faster, and the nadir is reached earlier and is lower.
It does not follow that renewable generation is fundamentally worse for frequency control. Inverter-coupled plants can change their output very quickly if they are designed and controlled accordingly. Possibilities include fast frequency-proportional control, synthetic inertia or grid-forming inverters, which set their own voltage and thereby respond in an inertia-like manner. The technical question is therefore no longer only how much rotating mass is present. What is also decisive: How fast is power changed? How long can it be sustained? Which measurement triggers the response? What requirements does the grid connection impose?
The nadir shows whether these answers suffice in practice. A reserve that only takes full effect after many seconds helps with the later course but improves the nadir only to a limited extent. A very fast but brief response can raise the nadir without securing the later equilibrium on its own. Frequency control therefore consists of several functions staggered in time: instantaneous reserve, FCR, and automatic and manual frequency restoration.
Typical misunderstandings
-
Energy instead of power: For the nadir, what counts is how quickly power is available at the moment of the disturbance, not the quantity of energy available over hours. A large storage unit that feeds in sluggishly helps the nadir less than a smaller, very fast plant.
-
Inertia equals security: High inertia slows the decline and buys time but does not replace balancing reserve. Low inertia is not automatically unsafe if fast supporting power is reliably available and the protection technology is matched to it.
-
Spatial effects: In an interconnected system, frequency is essentially a shared quantity. In a system split, however, a subnetwork can suddenly find itself with much less inertia and reserve and with a large imbalance. The possible nadir then shifts abruptly.
Institutional and economic context
The frequency nadir is neither a market price nor a policy target of its own. It results from technical characteristics, operating rules and procurement decisions. Transmission system operators determine the dimensioning, procure balancing reserve and monitor operation. Plant operators provide capabilities to the extent that connection rules, markets or contracts require it. Regulatory authorities help decide which costs are recognised and which ancillary services are remunerated or mandatory. When fewer synchronous generators are on the grid, inertia and fast power response must be provided in other ways. Possibilities include storage, grid-forming inverters, minimum requirements for plants, controllable loads or dedicated procurement products. Each solution has its own costs and limits.
Strictly speaking, the frequency nadir thus designates only the lowest frequency value after a sudden power disturbance. It does not explain why the disturbance occurred and does not describe security of supply as a whole. It does show, however, whether the system provides enough physical and control-related counteraction in the first seconds before protection thresholds are reached.
Sources
- Explanatory Note for FCR Dimensioning (Synchronous Area Operational Agreement Continental Europe) — ENTSO-E; unbekannt. Abschnitte zum Dimensionierungskriterium und zum Referenzstörfall
- Frequency Stability Evaluation Criteria for the Synchronous Zone of Continental Europe — ENTSO-E, Regional Group Continental Europe; unbekannt. Abschnitt zum normativen Störfall und zur Systemträgheit, Abbildung 1
- Frequency Containment Reserve – Aktivierung der Reserven — Deutsche Übertragungsnetzbetreiber (regelleistung.net); unbekannt. Abschnitt Aktivierung der Frequency Containment Reserve
- Verordnung (EU) 2017/2196 zur Festlegung eines Netzkodex über den Notzustand und den Netzwiederaufbau des Übertragungsnetzes — Europäische Kommission, Amtsblatt der EU L 312/54; 2017-11-24. Anhang, Tabelle zum automatischen Unterfrequenzlastabwurf
- Testplan gemäß Art. 4 Abs. 2 lit. g) der Verordnung (EU) 2017/2196 (Vorschlag der deutschen ÜNB) — Bundesnetzagentur / deutsche Übertragungsnetzbetreiber; 2020-09-22. Kapitel 4.1 Maßnahmen bei Frequenzabweichungen, 4.1.1 Unterfrequenzlastabwurfrelais
Related glossary entries
- grid frequency
- instantaneous reserve
- system inertia
- RoCoF
- FCR
- balancing reserve
- under-frequency load shedding
- power outage
- power electronics
- synthetic inertia
- grid-forming inverters
- ancillary services