Cycle ageing

Cycle ageing refers to the wear of a storage system caused by charging and discharging processes. The term is used mainly for a battery storage system, especially for lithium-ion batteries. Every use changes the cell a little, both physically and chemically. Active materials expand and contract, which can cause microcracks. Interface layers grow on the electrodes, for example the solid electrolyte interphase (SEI). Some lithium becomes permanently bound, and internal resistances rise. The result is usually a loss of usable storage capacity and often also a decline in the available power.

What counts as a cycle

A cycle does not necessarily mean charging the battery once from 0 to 100 percent and then discharging it completely again. In practice, people often work with full cycles or an equivalent full cycle: two discharges of 50 percent of the usable capacity each add up, in calculation terms, to one full cycle. This conversion is helpful but greatly simplified. This is because ageing does not depend linearly on cycle depth. A shallow discharge from 60 to 50 percent stresses the cell differently from a deep discharge from 100 to 10 percent, even if both add up to the same amount of energy over many operations. In ageing models for market operation, irregular charge profiles are therefore often broken down into individual partial cycles of different depths using counting methods such as the rainflow algorithm.

Distinction from calendar ageing

Cycle ageing must be distinguished from calendar ageing. The latter describes ageing due to time, state of charge and temperature, even when the storage system is hardly used. A battery that sits permanently fully charged in a warm environment can age considerably even though it goes through only a few cycles. Cycle ageing, by contrast, arises from actual use. Both effects take place at the same time and can only be separated approximately in real applications. Model calculations even show that they overlap: at high temperatures, a profile with shallower cycles but long rest periods can age faster overall than one with deeper cycles. The reason is that calendar ageing then predominates during the rest periods. For assessing a storage system, the distinction nevertheless remains important, because it makes different causes, operating strategies and costs visible.

Technical influencing factors

  • Cycle depth: The depth of discharge plays a central role. How strong its effect is can be seen in an example often cited in the literature for a small NMC cell: at 10 percent cycle depth it reached over 50,000 cycles, at 100 percent only about 500. As a result, the total energy throughput was many times higher with shallow cycles. Such values apply only to the cell in question and the test conditions.

  • Current load: The C-rate describes the charging or discharging current in relation to the nominal capacity. At 1C, a battery is, in calculation terms, fully charged or discharged in one hour, at 2C in half an hour, provided the battery management system allows it. In storage practice, the C-rate is often given approximately as the ratio of power to energy. A system with 100 kilowatt-hours that is charged at 100 kilowatts then operates at about 1C. High currents usually lead to greater heating and electrochemical stress. However, the effect is not always uniform and depends strongly on temperature.

  • Temperature: High temperatures accelerate above all side reactions and thus also calendar ageing. At low temperatures, fast charging can lead to lithium plating, that is, the deposition of metallic lithium. In addition, mechanical damage to the active materials becomes more prominent.

  • State-of-charge window and cell chemistry: Extreme states of charge close to 0 or 100 percent noticeably shorten service life. The medium state of charge, by contrast, has a rather weak and nonlinear effect. Different cell chemistries, such as lithium iron phosphate or NMC, react with different sensitivity to these factors.

Many battery systems therefore avoid extreme states of charge. If a home storage system is specified with a capacity of 10 kilowatt-hours, this amount of energy is not automatically used in full between technically empty and technically full. The battery management system often keeps buffers free in order to extend service life. Whether a figure refers to the gross or the usable net capacity should therefore be checked in the data sheet. The usable capacity is already the result of a technical and economic trade-off between maximum utilisation and limited ageing.

Reading cycle numbers correctly

Cycle ageing is often reduced to a single number, for example: a battery lasts 4,000 or 8,000 cycles. Without boundary conditions, such a figure says little. It usually applies only to a specific temperature, cycle depth and charging power, as well as to a defined end of life. Often this limit is 80 percent remaining capacity, measured by the state of health. After this limit is reached, a battery does not suddenly become unusable. It simply stores less energy than at the beginning or meets certain performance requirements less well. Service-life figures are therefore not expiry dates but technical thresholds for a particular use.

In debates, years, cycle numbers and warranty conditions are often mixed up. A warranty can, for example, guarantee a minimum remaining capacity after a certain time or after a certain energy throughput. Energy throughput is the total amount of energy charged or discharged over the service life. An example: 10 kilowatt-hours of usable capacity times 4,000 equivalent full cycles gives, in calculation terms, 40 megawatt-hours of throughput. This figure often reflects different usage profiles better than a mere cycle number. However, it also depends on how gently the storage system is operated.

Legal framework in the EU

In the EU, Battery Regulation (EU) 2023/1542 governs how information on durability must be disclosed. Since 18 August 2024, rechargeable industrial batteries with a capacity of more than 2 kWh, including stationary battery storage systems, must be accompanied by documentation with values on electrochemical performance and durability in accordance with Annex IV. This includes the expected lifetime under reference conditions, expressed in cycles and calendar years. In addition, power and power fade are required. Also since 18 August 2024, the battery management system of stationary storage systems must contain up-to-date data for determining the state of health and expected lifetime in accordance with Annex VII. Binding minimum values for industrial batteries are to be set by delegated act. They apply at the earliest from 18 August 2027 or 18 months after the entry into force of this act, whichever is later. This status applies to the consolidated version of 13 August 2026.

Significance in the power system

In the power system, cycle ageing matters because storage systems are not loss-free machines for shifting electricity. Anyone who charges a battery and later discharges it incurs ageing costs in addition to conversion losses. These costs are real, even if they do not appear individually on any electricity bill. A storage operator must decide whether a charging and discharging operation is worthwhile. The revenue from price differences, grid services or self-consumption must cover the losses, the capital costs and the additional ageing. Cycle ageing thus becomes a component of the marginal costs of flexibility. In dispatch models for electricity markets, ageing costs are therefore often factored into the bidding strategy per cycle depth.

This affects different applications. A home storage system increases the self-consumption of photovoltaic electricity but ages with every additional cycle. A large-scale storage system can, in arbitrage, take in electricity at low prices and release it at high prices. Whether this is worthwhile depends on whether the price spread is large enough. For balancing energy or other ancillary services, high power availability is often required without large amounts of energy being converted constantly. Often these are many shallow cycles around a medium state of charge. This stress differs from daily deep cycles lasting several hours. Technical ageing therefore influences which revenue models are viable.

For system planning, energy, power and cycles must be clearly separated. The storage capacity in kilowatt-hours indicates how much energy can be stored. The power in kilowatts or megawatts indicates how quickly charging or discharging can take place. Cycle ageing describes how strongly use changes the storage capability over time. A large storage system with high power is assessed differently in economic terms if many deep cycles shorten its service life. Conversely, a moderately used storage system can be valuable over many years even though its annual amount of energy remains small. Because calendar ageing continues even without use, however, very infrequent cycling is not automatically the economically best strategy.

A common misunderstanding is to regard every additional use of storage as good for the system. If a battery storage system charges and discharges only because short-term price signals allow it, this can make business sense. For the overall system, what counts is whether renewable electricity is thereby better integrated, grid bottlenecks are reduced, peak load is lowered or security of supply is supported. Cycle ageing acts here as a cost component that prevents use from being automatically equated with benefit.

Rules, incentives and other flexibility options

Institutionally, cycle ageing becomes important where rules steer the use of storage. Market prices, grid charges, connection conditions, support programmes and prequalification rules influence which mode of operation is worthwhile. A home storage system for self-consumption optimisation follows different incentives from a large-scale storage system that responds to price signals and balancing energy markets. If grid charges or levies favour or burden certain charging and discharging operations, this changes the number of cycles and thus the ageing. Technical degradation and operating rules should therefore be considered together.

Cycle ageing is also one reason why flexibility is not arbitrarily interchangeable. Load shifting in industrial processes, flexible heat pumps, electrolysers, grid expansion and battery storage can fulfil similar tasks but have different cost structures. With batteries, part of the costs is directly tied to throughput. With other options, costs arise rather from comfort limits, process risks, investments in control technology or lost production.

Distinction from efficiency

Efficiency losses must be distinguished from cycle ageing. Efficiency indicates what share of the energy fed into storage can later be withdrawn again. Cycle ageing, by contrast, describes the long-term change of the storage system through use. Both effects act together and are partly interdependent. With every cycle, energy is lost through conversion and heat. Over many cycles, the storage system loses part of its original capability. If internal resistance rises with ageing, efficiency often falls as well. For cost calculations, emission balances and operating strategies, both effects must be taken into account.

Cycle ageing shows that storage systems provide a limited technical resource: the shifting of energy over time under wear. The term alone does not decide whether a storage system makes sense. But it makes visible which costs and consequences for service life are associated with its use. Used precisely, it separates the question of technical storage capability from the question of how often, how deeply, how fast and for what purpose a storage system should be used.